YVZ4V-U ,YVZ4V-R, NYBY

Place of use

Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage. 

Structure

  • Solid or stranded copper conductor.
  • PVC insulation.
  • Filler.
  • Galvanized round steel wires.
  • PVC outer sheath.

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C
28-32000001 4x1.5 14.0 360 1000 12.1 26 18,5
28-32000002 4x2.5 15.0 440 1000 7.41 34 25
28-32000003 4x4 17.0 580 1000 4.61 44 34
28-32000004 4x6 18.0 700 1000 3.08 56 43
28-32000005 4x10 21.0 980 1000 1.83 75 60
28-32000006 4x16 23.5 1300 1000 1.15 98 80
28-32000007 4x25 27.0 1850 1000 0.727 128 106
28-32000008 4x35 29.5 2350 1000 0.524 157 131
28-32000009 4x50 34.0 3100 1000 0.387 185 159
28-32000010 4x70 39.0 4450 1000 0.268 228 202
28-32000011 4x95 44.5 5800 500 0.193 275 244
28-32000012 4x120 49.0 7100 500 0.153 313 282
28-32000013 4x150 53.5 8600 500 0.124 353 324
28-32000014 4x185 59.0 10500 250 0.0991 399 371
28-32000015 4x240 67.0 13400 250 0.0754 464 436

Technical Info